Product Details:
Payment & Shipping Terms:
|
Rated Input Power: | 198W | Rated Input Current: | 0.9A |
---|---|---|---|
Rated Cooling Capacity: | 400W | Cooling Method: | Compressor, Active Cooling |
Noise: | ≤55dB | Application: | Outdoor Telecom Base Station Cabinet |
Protection Level: | IP55 | Working Humidity: | ≤95% |
High Light: | outdoor enclosure air conditioner,server cabinet air conditioner |
400W Active Cooling Outdoor Cabinet Air Conditioner Cutomized Low Noise
Quick Details:
Place of Origin: Shenzhen, China (Mainland) | Rated Cooling Capacity : 400W |
Brand Name: ESTEL | Rated Heating Capacity:300W/500W(optional) |
Model: TC06-40JFH/01 | Dimension: H×W×D 520×360×187mm |
Product Name: Outdoor Enclosure Air Conditioner | Input Voltage: AC220V/50Hz |
Certification: ISO9001, CE, 3C, FCC, TLC | Rated Input Current: 0.9A |
Cover: including outer cover | Rated Input Power: 198W |
Color: grey | Working Temperature: -20°C ~ +55°C |
Protection Level: IP55 | Noise: ≤55dB |
Installation Mode: door mounted, side mounted | Refrigerant: R134a |
Support OEM | Cooling Method: compressor, active cooling |
Payment & Shipping Terms:
Minimum Order Quantity: | 1 set |
Price: | negotiation |
Payment Terms: | L/C, D/A, D/P, T/T, Western Union |
Supply Ability: | 15,000 sets per month |
Delivery Time: | 10-15 working days |
Packaging Details: | carton + wooden case |
1. Specifications
(1) Technical Parameters
Environmental Performance | working environmental temperature | -20°C ~ 55°C |
storage temperature | -40°C ~ 70°C | |
working humidity | ≤95% | |
Thermal Performance | rated cooling capacity |
450W(L35 L35) 400W(L25 L35) |
Electrical Performance |
rated input current |
1.0A(L35 L35) 0.9A(L25 L35) |
rated input power |
220W(L35 L35) 198W(L25 L35) |
|
input voltage | AC220V/50Hz (185V~264V) |
Dimension Diagram: H×W×D: 520×360×187mm
Size Model |
Specs | A | B | C | D | E | F | G | H | I | J | K |
TC06-120JFH/01(KT041) | 1200W | 300 | 401 | 450 | 600 | 671 | 695 | 190 | 220 | 650 | 378 | 424 |
Size Model |
Specs | A | B | C | D | E | F | G | H | I | J | K |
TC06-120JFH/01(KT041) | 1200W | 300 | 401 | 450 | 600 | 671 | 695 | 190 | 220 | 650 | 378 | 424 |
2. Description
TC06-40JFH/01 Air Conditioner is a full automation temperature control product. It uses intelligent controller to control the whole system of the air conditioner. According to the variation of environment temperature, the intelligent controller can automatically detect, operate and record the whole system’s operating time, power consumption, event and historical data. It can store 100 event records and 1280 historical data records, and can enquire 256 days’ daily record information.
Cabinet air conditioner is actively cooling with compressor, and it will remove the heat inside the cabinet to outside. It also can keep the dust and heat outside the cabinet, avoiding problems from using fan. The inside cabinet can be maintained at an ideal temperature for electrical components which effectively guarantees the stability of the electronic equipment and improves the reliability of the whole system.
3. Application
The air conditioner is widely applied in outdoor telecom cabinet, battery cabinets, electric cabinets, industry control cabinets, small and medium sized telecom room, UPS room, outdoor base station room, etc.
Wiring Ports:
L N PE : power supply port (voltage input: 220VAC±15% 50Hz)
F+ F- : direct ventilation output port
AL1 AL2: general alarm output port
A+ B- SGND: RS485 communication port
N: not connected pin
ET731 intelligent air conditioner controller is a universal intelligent controller, controlling with highly integrated STC SCM. It can intelligently control thermostatic cabinet air conditioner working and hydrogen exhausting, including functions such as fault self diagnosis, power-on self start, or restart after unexpected failure caused by other reasons. The controller is compatible with all types of air conditioners in the market.
The controller, with the features of advanced performance, easy installation and setting, are widely used in telecom cabinet, small and medium sized telecom room, UPS room, outdoor base station room, etc.
ET731 uses English interfaces, which can be operated easily. All the operations can be realized with four buttons. The following is the control board diagram:
a. Check operating parameters of key parts inside air conditioner, namely observation parameter. Operation steps:
Observation Parameter: on the left of line 1 is Parameter No. (PAnn); on the right of line 1 is parameter value. Line 2 shows the remark of the parameter.
b. Revise operating parameters of air conditioner, namely control parameters. Operation steps:
Control Parameter: on the left of line 1 is Parameter No. (PCnn), on the right of line 1 is parameter value. Line 2 shows the remark of the parameter.
c. Revise basic parameters of air conditioner. Operation steps:
Basic Parameter: on the left of line 1 is Parameter No. (PBnn), on the right of line 1 is parameter value. Line 2 shows the remark of the parameter.
d. Manual Operation Mode:
Operation steps:
Enter the interface to select “Cool” (cooing), “Heater” (heating), “Air” (direct ventilation) to conduct manual start (ON) and stop (OFF) operation.
e. Event Query Mode:
Operation steps:
9. Packing and Shipping
Our Delivery Agent
The goods can be shipped by sea, by air, by courier, by land, by train, etc.
Besides the following delivery agent, we can also look for the delivery agent with the best price in china if you need us to do for you.
10. Our Contact Information
Mobile Phone: 0086-13752765943
Telephone: 0086-0755 66600941
Email: info@estel.com.cn
lxf.estel@hotmail.com
Skype: fiona.liang10
Contact Person: Fiona Liang
Tel: +8613752765943 / 86-0755 23592644