Dual Bay 40U Outdoor Telecom Cabinet for Inverter with Dual 1500W AC IP55 with 5 Battery Trays for Solar Base Station Anti Theft Design

Basic Properties
Place of Origin: China
Brand Name: ESTEL
Certification: CE UL FCC
Trading Properties
Minimum Order Quantity: 1 SET
Price: USD300-USD1000
Payment Terms: T/T, Western Union
Supply Ability: 5000
Product Summary
Dual Bay 40U Outdoor Telecom Cabinet for Inverter with Dual 1500W AC IP55 with 5 Battery Trays for Solar Base Station Anti Theft Design Product Description This is a specialized outdoor dual-bay cabinet designed specifically to house a single high-power inverter alongside substantial battery backup. ...

Product Details

Size: W*D*H 1600*1000*2000mm
Working Temperature: -40°C ~ +55°C
Storage Temperature: -40°C To +85°C
Available User Space: 34U Standard 19” Rail
Heat Insulation: PEF
Cabinet Door: One Front Door
Dimension: H*W*D 1225*900*900mm
Service: OEM.ODM
Ip Rating: IP55
Color: RAL7035 Light Grey
External Size: W× D×H 1500 ×900 ×1800mm
Door Stopper: Included
Cableentry: Bottom And Top Cable Entry With Glands
Device: 19 Inch Devices Can Be Installed Inside
One Compartment: Equipment Compartment
Product Description

Dual Bay 40U Outdoor Telecom Cabinet for Inverter with Dual 1500W AC IP55 with 5 Battery Trays for Solar Base Station Anti Theft Design

 

 

Product Description

This is a specialized outdoor dual-bay cabinet designed specifically to house a single high-power inverter alongside substantial battery backup. Featuring two 19-inch 40U compartments with no middle partition, it provides a wide, uninterrupted internal space perfect for bulky inverter installation. The double-wall insulated construction and dual 1500W air conditioners ensure that your sensitive equipment operates in a stable, temperature-controlled environment, even in extreme weather.

 

 

Applications

Specifically engineered for outdoor solar photovoltaic stations, energy storage systems, railway signal control points, and macro base stations that require large inverters and multi-row battery banks. Ideal for sites demanding high power conversion and reliable backup power in harsh outdoor environments.

 

 

Technical Parameters

Model: Two bay 40U

 

External Dimensions: H2000mm × W1600mm × D1000mm (including 100mm plinth height)

 

Internal Space: Two compartments, 19 inch, 2*40U, no middle partition

 

Materials: Double layer galvanized steel sheet, outer thickness 1.5mm, inner thickness 0.8mm with 20mm PEF insulation

 

Protection Level: IP55

 

Coating: RAL7035, two layers anti-rusted paint coating

 

Cooling: 2 sets of 1500W Air Conditioner (AC220V, 50Hz, with dehumidification and salt spray resistance, C4 grade, 304 stainless steel cover)

 

Lighting: 2pcs LED Lamp (AC220V, 50Hz, 1pc with switch per compartment)

 

Sensor: 2pcs Door Sensor

 

Package: Wooden case (H2180mm×W1700mm×D1270mm), weight 460 kg

 

 

Features

Dual-compartment design with no central partition, providing maximum continuous space for a single large inverter.

 

Includes 5pcs battery fixed trays, 2pcs 3U panels for DIN rails, 1pc 5U circuit breaker mounting plate, and 1pc inverter mounting plate.

 

Double-layer galvanized steel with PEF insulation offers excellent thermal insulation and high anti-corrosion performance.

 

Equipped with dual 1500W air conditioners featuring dehumidification and C4-grade salt spray resistance for coastal or humid areas.

 

Two front doors with anti-theft three-point locks, inner hinges, and additional padlock options for maximum security.

 

 

Operation Guide

Installation: Position the cabinet on a flat concrete foundation using the 100mm plinth. Secure it tightly using anchor bolts. Ensure proper grounding for both doors and the main body.

 

Battery Mounting: Place the battery modules onto the 5 fixed battery trays. Secure them to prevent movement. Ensure the battery cables are routed to the inverter using the internal cable management channels.

 

Inverter Setup: Mount the large inverter onto the dedicated inverter mounting plate. Route the DC input (from batteries) and AC output cables through the bottom cable entry points.

 

Circuit Breaker & DIN Rail: Install your circuit breakers on the 5U mounting plate and your DIN rail components on the 3U panels.

 

Maintenance: Regularly clean the air filters on both air conditioners. Check the dehumidification function for normal operation, inspect door seals for tightness to maintain the IP55 rating, and verify LED lighting functionality.

 

 

 