IP55 Outdoor Cabinet Air Conditioner Cooling Double Wall Base Station Cabinet
1.Outdoor Cabinet Air Conditioner Cooling Double Wall Base Station Cabinet Overview
IP55 Outdoor Cabinet Air Conditioner Cooling Double Wall Base Station Cabinet provides flexible size options. The cabinets system ca
n support Electrical equipments, PDU, Backup batteries, Environment Mornitoring unit and etc. It can support water sensor, door sensor, temperature sensor, smoke sensor, and humidity sensor inside. This series enclosure offers the ideal enclosure solution to build the whole base station inside.
2. Outdoor Cabinet Specifications
2.1 External Size:W*D*H 750*750*1750mm
2.2 Cabinet Structure:Double wall with insulation, Sandwich structure.
2.3 Cabinet Layout:One compartment for installing 19” equipment
2.4 Equipment Installation Method:19” rack
2.5 Material:Galvanized steel, 1.5mm thick outer plate, 0.8mm thick inner plate
2.6 Protection Level:IP55
2.7 Cabinet Inlets:From cabinet bottom
2.8 Lighting:DC48V LED lamp
2.9 Heat Insulation:PEF
2.10 Grounding Protection:Copper bar
2.11 Cooling System:Fans,Air conditioner optional
2.12 Alarm sensors:Door sensor, water sensor, smoke sensor, temperature and humidity sensor
2.13 Cabinet Lock:Anti-theft three point lock(support padlock)
2.14 Package:Wooden case with pallets
2.15 Certificates:CE
3.Cable Inlet
4. Cabinets Dimentions
5. Grounding Protection
5.1The cabinet includes grounding copper bar with anti-corrosion coating. There are enough screws for wiring connection terminals.
5.2The metal part of the cabinet should be interconnected and be connected with grounding bar. Connection resistance between any two points is lower than 0.1Ω.
5.3Protective earthing of other equipments inside the cabinet should be connected to the grounding bar.
6. Theft Proof Design
6.1 Theft proof door lock design
Damage resistance of the theft proof lock meets GA/T 73-1994 “Mechanical Anti-theft Lock” class B requirement, supporting padlock.
6.2 Connection and Fastening
Use anti-loose threaded connection as structure and bearer connection. Anchor bolt for fixing cabinet use hot dip galvanized bolts.
Door hinges use inner hinge mode.
6.3 Appearance and Surface Treatment
Cabinet surface coating is outdoor special powder coating, with white gray color (PANTONE 428C). The coating complies with GB/T 3181-2008 requirement.
7.Cabinet Leading Time
It will take about 10-15 days. The exact lead time need to be confirmed according to the quantity of order.
8. Our Delivery Agent
The goods can be shipped by sea, by air, by courier, by land, by train, etc.
Besides the following delivery agent, we can also look for the delivery agent with the best price in china if you need us to do for you.