Product Details:
Payment & Shipping Terms:
|
External Dimension: | W×D×H 650×600×1951mm | Material: | Aluminum AL5052, Double Wall, 1.5mm Thick Outer Plate, 1.5mm Thick Inner Plate |
---|---|---|---|
Heat Insulation: | There Are Heat Insulation Between Inner Wall And Outer Wall. The Insulation Material Is 20mm PEF. | Environment Monitoring Unit: | 1U, DC48V, Support SNMP Communication |
Cooling: | Fan System: | Layout: | The Upper Part Is Standard 19” Installation Rack (22U), The Lower Part Is Two Battery Shelves For Installing Two String Batteries. |
Solar Radiation Intensity: | 1120 ×(1±5%)W/m2 | Relative Humidity: | 5% ~ 100% |
Air Pressure: | 62kpa ~ 101kpa (similar To 0m ~ 5000m Altitude) | ||
Highlight: | outdoor equipment cabinet,power supply cabinet |
Double Wall Aluminum AL5052 Outdoor Power Cabinet / Outdoor Telecom Cabinet With SNMP Monitoring
1. Application
The Outdoor Telecom Cabinet is mainly used in wireless communication base station, such as 4G system, communication/network integrated service, access or transmission switching station, emergency communication or transmission, etc.
2. Features
(1) The cabinet is dustproof, sunproof and rainproof, used in outdoor environment.
(2) Cabinet cooling: fans.
(3) Include grounding bar.
(4) Include cable entry plate at cabinet side and cabinet bottom.
(5) Coating: outdoor powder coating RAL7035.
(6) Include documents holder, laptop table, filter, and door stopper on cabinet door.
(7) Include cable duct.
(8) Include battery protection bracket for each battery string.
(9) Include bind cover on cabinet right side.
(10) Include base mounting frame.
3. Technical Parameters
Item |
Type |
Technical Parameter |
Structure |
Dimension |
External Dimension: W×D×H 650×600×1951mm |
Layout |
1 compartment |
|
Equipment Installation Method |
The upper part is standard 19” installation rack (22U), the lower part is two battery shelves for installing two string batteries. |
|
Door |
With one front door, and anti-theft three point lock for outdoor cabinet (support padlock). |
|
Material |
Aluminum AL5052, double wall, 1.5mm thick outer plate, 1.5mm thick inner plate |
|
Heat Insulation |
There are heat insulation between inner wall and outer wall. The insulation material is 20mm PEF. |
|
Ingress Protection |
IP55 |
|
Temperature Control |
Cooling |
Fan System: Include 3 fans; Power Supply: DC48V; Air inlet at front door and air outlet at cabinet top. When temperature inside cabinet is above 25 °C, fan will start to work; when temperature inside cabinet is below 25 °C, fan will stop working. Fan start working temperature is adjustable, can be set at different temperature according to need, factory default is 25 °C. The temperature sensor detect the temperature and send information to environment monitoring unit. |
Lighting |
LED lamp |
DC48V LED lamp |
Temperature |
Temperature |
Working Temperature: -40°C ~ +55°C |
|
|
Storage Temperature: -50°C ~ + 70°C |
|
|
Transport Temperature: -50°C ~ +70°C |
Humidity |
Relative Humidity |
5% ~ 100% |
Pressure |
Air Pressure |
62kpa ~ 101kpa (similar to 0m ~ 5000m altitude) |
Radiation Intensity |
Solar Radiation Intensity |
1120 ×(1±5%)W/m2 |
4. Accessories List
No. |
Item |
Quantity |
Unit |
Specs |
1 |
Outdoor Telecom Cabinet |
1 |
PC |
(1) External Dimension: W×D×H 650×600×1951mm (2) One compartment (3)With one front door, and anti-theft three point lock for outdoor cabinet (4) Material: aluminum, double wall, 1.5mm thick outer plate, 1.5mm thick inner plate. With thermal insulation. |
2 |
Fan System |
1 |
PC |
Include 3 fans; Power Supply: DC48V; |
3 |
Environment Monitoring Unit |
1 |
PC |
Model: NEM-500-SNMP 1U, DC48V, support SNMP communication |
4 |
Water Sensor |
1 |
PC |
Model: NSW-K1P5 |
5 |
Smoke Sensor |
1 |
PC |
Model: JTY-GD-T12 |
6 |
Temperature and Humidity Sensor |
1 |
PC |
Model: NSTH-A1T4 |
7 |
Door Sensor |
1 |
PC |
Model: M520 |
8 |
Tilt&Shock Sensor |
1 |
PC |
Model: NSS-K1A1 |
9 |
LED Lamp |
1 |
PC |
DC48V |
10 |
LED Lamp Switch |
1 |
PC |
Control LED lamp on/off. LED lamp will turn on when cabinet door is opened, and will turn off when cabinet door is closed. |
11 |
AC Power Distribution Unit |
1 |
PC |
1×80A 2P, 1×20A 2P, 1×6A 2P L1+L2+N+E terminal |
12 |
Package |
1 |
PC |
Wooden Case |
5. Cabinet Dimension
4. Air Flow
Contact Person: Fiona Liang
Tel: +8613752765943 / 86-0755 23592644