12U Hybrid Power Rectifier System 16kW Combined PV Rectifier 96% Efficiency

Basic Properties
Place of Origin: Shenzhen, China (Mainland)
Brand Name: ESTEL
Certification: ISO9001, CE, 3C, FCC, TLC
Trading Properties
Minimum Order Quantity: 1 set
Price: 715-4286 usd
Payment Terms: T/T, L/C,D/A, Western Union, Paypal, etc
Supply Ability: 5,000 sets per month
Product Summary
12U Hybrid Power Rectifier System 16kW Combined PV Rectifier 96% Efficiency Introduction This is not a rectifier shelf with a solar input bolted on. The 12U hybrid system runs six 3kW PV modules and four 4kW rectifier modules into a single DC bus, both feeding the same -53.5VDC output. Solar and ...

Product Details

Highlight:

12U hybrid power rectifier system

,

16kW combined PV rectifier

,

96% efficiency telecom power system

Type: Hybrid Telecom Rectifier
Dimension: 12U*482mm*350mm
Rectifier Capacity: 16kW
PV Capacity: 18kW
Rectifier Module: 4kW
PV Module: 3kW
Rectifier Efficiency: 96%
Mounting: 19-inch Mount
Product Description

12U Hybrid Power Rectifier System 16kW Combined PV Rectifier 96% Efficiency

Introduction

 

This is not a rectifier shelf with a solar input bolted on. The 12U hybrid system runs six 3kW PV modules and four 4kW rectifier modules into a single DC bus, both feeding the same -53.5VDC output. Solar and grid coexist on the bus simultaneously — no transfer switch, no contactor sequencing, no gap when clouds roll in.

 

That architecture matters for off-grid and weak-grid sites: the PV modules carry load whenever the sun is up, the rectifiers pick up the remainder, and the battery sits behind a dedicated breaker waiting for both to falter.

 

6 × 3kW PV (18kW) plus 4 × 4kW rectifiers (16kW), both strings N+1 redundant. Lose a PV module and the rectifiers absorb the difference; lose a rectifier and the PV side keeps producing.

 

96%+ efficiency on both module types. The rectifier modules hold >96% across their 4kW rating; the PV modules match it. In a naturally cooled 12U chassis, that efficiency headroom is what keeps internal temperatures manageable without fans on the shelf itself.

120–425VDC PV input window. Wide enough to accept strings without aggressive MPPT configuration — rated at 340VDC, comfortable across the full range.

AC Distribution

Dual 125A 2P input breakers, one designated as backup. If the primary feed trips or is taken out for maintenance, the second breaker is already landed and ready — no re-termination, no downtime waiting for an electrician.

 

AC output is 110VAC: 2 × 63A 1P and 3 × 32A 1P circuits for site equipment. Both AC and DC sides carry 20/40kA (8/20µs) SPDs, so a surge on either bus has somewhere to go before it reaches the electronics.

DC Distribution

Breaker Rating Purpose
Battery 2 × 125A 1P Dedicated battery isolation
BLVD 1 × 63A 1P Critical load feed
Load 3 × 20A 1P + 6 × 10A 1P Mixed equipment branches
DC input 6 × 25A 2P PV/DC source inputs

 

Output voltage is adjustable from -43VDC to -58VDC, nominal -53.5VDC. The 63A BLVD plus the 20A and 10A branches give you a distribution panel that covers both a heavy critical load and a spread of smaller devices without blank positions.

Module Details

Rectifier module: 85–300VAC input (rated 220VAC), 4,000W at 176–300VAC, 55A max DC output, ≥0.99 power factor, THD ≤5%, forced cooling, 1U, ≤2kg. Full output to 50°C, operating range -40°C to +75°C.

 

PV module: 120–425VDC input (rated 340VDC), 3,000W at 200–425VDC, same 55A max output and efficiency figures, same 1U/≤2kg form factor, same temperature envelope.

 

Both module types are the same physical size — a PV module and a rectifier module swap into the same slot. That's a deliberate design choice: field spares are interchangeable, and a site can be rebalanced between solar and grid capacity by moving modules, not replacing shelves.

Control and Monitoring

The MC2900 controller provides 2 AI, 6 DI, and 6 DO, with RS485 and SNMP communication and an LCD for local readout. Standard stuff, but worth noting that SNMP is native — no gateway card.

Mechanical

Parameter Value
Dimensions 482.5mm W × 350mm D × 12U H
Weight ≤50kg (without modules)
Cooling Natural (shelf); forced (modules)
Installation 19-inch rack mount
Maintenance Front access, module-level replacement
Protection IP20

Environment

Operating -40°C to +65°C (full output below 50°C), storage -40°C to +70°C, humidity 5–95% non-condensing, altitude 0–3000m with derating above 2000m (1°C per 200m).